The Two-Wire Loop: Power, Transmitter, PLC Input
In industrial process automation, a two-wire 4–20 mA pressure transmitter operates on a shared current loop. Under this configuration, the same pair of copper conductors delivers direct-current (DC) operating power to the field instrument and returns the continuous analog measurement signal to the programmable logic controller (PLC). Unlike four-wire devices that require dedicated power cables, a two-wire transmitter functions as a series-connected current regulator powered entirely by the loop voltage.
According to technical guidance from SEGMENsensor, establishing this series circuit requires a precise loop order:
- Connect the positive terminal of the external DC power supply to the positive terminal of the pressure transmitter: Power supply (+) → Transmitter (+).
- Connect the negative terminal of the pressure transmitter to the positive analog input terminal of the PLC: Transmitter (−) → PLC AI (+).
- Connect the negative analog input terminal of the PLC back to the negative terminal of the DC power supply: PLC AI (−) → Power supply (−).
This sequence creates a single continuous electrical circuit connecting the power supply, field transmitter, and PLC input channel in series. Current flowing through the loop is regulated by the transmitter in proportion to the sensed process pressure. Because terminal designations differ across manufacturers, technicians must check their specific PLC and power supply documentation to identify the exact terminal labels and channel configurations.
Why 4 mA Is the Live Zero
Industrial current loops use 4 mA rather than 0 mA to represent the bottom of the measurement range. This offset is referred to as a live zero. The vendor guide highlights three key functional reasons for maintaining a 4 mA baseline:
- Fault detection: A complete loss of current (0 mA) indicates a physical circuit fault, such as a severed wire, a loose terminal, or a dead power supply. If the measurement scale started at 0 mA, the control system could not differentiate between zero pressure and a broken circuit.
- Instrument power: Because a two-wire transmitter has no independent power leads, it draws its operating power directly from the loop. The baseline 4 mA current energizes the internal sensing element and signal conditioning electronics without registering as process pressure.
- Resistance immunity: In a closed series circuit, the regulated current remains uniform across the entire loop. Unlike voltage signals that experience signal loss over extended distances due to cable resistance, current signals reach the PLC receiver without attenuation from moderate wire runs.
The 250 Ω Load and 1–5 V Conversion
Many PLC analog input modules sample voltage rather than measuring loop current directly. To convert the 4–20 mA current into a readable 1–5 V potential difference, the input circuit uses a 250 Ω load resistor (frequently called a burden or shunt resistor).
Under Ohm’s law (voltage equals current multiplied by resistance):
- At 4 mA (0.004 A): 0.004 A × 250 Ω = 1.0 V.
- At 20 mA (0.020 A): 0.020 A × 250 Ω = 5.0 V.
The vendor documentation identifies two common hardware approaches for this load resistance:
- Internal 250 Ω resistors: Many modern PLC analog input cards contain an integrated 250 Ω resistor. When the card is configured for current mode via physical jumpers or software settings, this internal resistor is switched into the channel circuit automatically.
- External parallel resistors: Older analog input cards or voltage-only input channels do not include an internal resistor. For these modules, technicians must connect a discrete 250 Ω precision resistor in parallel across the PLC AI (+) and PLC AI (−) terminals to generate the 1–5 V signal.
Technicians must verify the hardware design in the PLC manual before wiring. Installing an external resistor on a channel with an active internal resistor cuts the effective circuit resistance in half, distorting the signal reading.
Scaling the Pressure Signal
To convert the measured loop current into engineering units within the PLC program, the controller applies linear scaling across the transmitter span. The SEGMENsensor technical documentation provides the linear conversion formula:
I = 4 + 16 × (value ÷ span)
In this equation, I is the loop current in milliamperes, value is the measured process pressure, and span is the calibrated measurement range of the transmitter.
For example, with a transmitter calibrated for 0 to 10 bar (a 10 bar span), a process pressure of 6 bar produces the following current:
I = 4 + 16 × (6 ÷ 10) = 4 + (16 × 0.6) = 4 + 9.6 = 13.6 mA
Passing this 13.6 mA current through a 250 Ω resistor develops 3.4 V at the PLC analog input terminals (0.0136 A × 250 Ω = 3.4 V).
| Pressure (bar) | Span Percentage | Loop Current (mA) | Voltage at 250 Ω Load (V) |
|---|---|---|---|
| 0.0 | 0% | 4.0 mA | 1.0 V |
| 2.5 | 25% | 8.0 mA | 2.0 V |
| 5.0 | 50% | 12.0 mA | 3.0 V |
| 6.0 | 60% | 13.6 mA | 3.4 V |
| 10.0 | 100% | 20.0 mA | 5.0 V |
Pre-Wiring Checklist
Before applying power or introducing process pressure, review the following practical steps:
- Check the PLC analog module manual to verify whether the 250 Ω burden resistor is internal, jumper-selected, or requires an external parallel installation.
- Confirm that the DC power supply voltage meets the transmitter operational requirements.
- Verify series loop polarity: Power supply (+) to Transmitter (+), Transmitter (−) to PLC AI (+), and PLC AI (−) to Power supply (−).
- Ground the cable shield at the control panel end only, leaving the field sensor end floating to prevent ground loops.
- Confirm that PLC analog scaling matches the transmitter calibrated range (such as 0–10 bar mapped to 4–20 mA or 1–5 V).
What This Article Does Not Claim
To maintain rigorous technical limits, note the specific scope of this explainer:
- Single-source guidance: This explainer relies on a single vendor technical guide from SEGMENsensor. A second independent source was not confirmed.
- No standard citations: This article does not claim compliance with or reference clauses from international standards such as IEC 60381-1.
- Equipment manual dependency: Generic loop diagrams cannot replace official documentation. Final terminal numbers, module burden capabilities, and supply voltage ranges must be confirmed directly in the manuals for the specific PLC and transmitter models in use.